Xp-5M & Xp-5C Modules - Notifier 1010 Installation And Programming Manual

Intelligent fire detection and alarm system
Hide thumbs Also See for 1010:
Table of Contents

Advertisement

1010/2020 I
A
NSTALLATION
ND
XP-5M & XP-5C M
The XP-5 Control and XP-5 Monitor modules are 5 separate modules and addresses mounted on
one circuit card, the address is chosen by one rotary switch and one slide switch.
The rotary switch selects the address in increments of ten, and the slide switch selects either 0 or 5.
Eg; address 52- the rotary switch will be 5, and the slide switch will be 0.
Address 52 will be the third point on the XP-5 card.
The wiring of both the XP-5C and XP-5M are wired exactly as the CMX-2 and MMX-101 devices,
the only difference being that they share the same loop connection.
Address Sw1-5 set ON,
If not used, set OFF.
For Future Use, Set
SW1-5 Off
Note: Each output on the XP-5C is selectable via a switch.
Monitored output = Switch Depressed (Above Line)
Relay Output = Switch Not Depressed (Below Line).
Monitored output circuits are to be wired as per a CMX-2 and connected to the XP5-C as shown.
P
M
ROGRAMMING
ANUAL
ODULES
C
OPYRIGHT
© 2000, N
I
P
OTIFIER
NERTIA
TY
L
TD
P
27
AGE