Zone Boundary (5=Zbnd); External Equipment - Notifier 1010 Installation And Programming Manual

Intelligent fire detection and alarm system
Hide thumbs Also See for 1010:
Table of Contents

Advertisement

1010/2020 I
A
NSTALLATION
ND
Z
B
ONE
OUNDARY
The 1010/2020 can make use of up to 240 software-defined "zones." These zones can be either
forward–activated (FZON) or reverse–activated (RZON), depending upon the particular installation
requirements. These forward and reverse zones are grouped separately, with the forward group
always preceding the reverse group. The highest forward-activated zone in the system is the Zone
Boundary, which can be in the range of Z001 - Z239. (For an explanation of software zones, refer to
What is a Software Zone on page 54).
Unless the use of complex Control-By-Event or Cooperative Control-By-Event Equations is required
in the system, set the Zone Boundary to Z99.
The following programming example illustrates setting the Zone Boundary for zone 99.
PRESS.1=INST, 2=STY, 3=TDLY, 4=AVPS, 5=ZBND, 6=EXTEQ, 7=LOCP, 8=ISIB, 9=PARM 5
ENTER.ZXXX.OF.HIGHEST.FORWARD.ACTIVATED.ZONE.IN.SYSTEM
E
E
XTERNAL
QUIPMENT
Option 6 allows the changing of any optional features, such as the following:
Terminal Supervision
Terminal Status Line
Auxiliary Printer
Monitoring
Control Module Reporting
NONA/NOA Module
Reporting
Devices Purchased after
11/91
LED LATCH
Printer Error Continue
Bidirectional Copy
Printer Fault Inhibit
Printer Reports
Redirected to
P
M
ROGRAMMING
ANUAL
(5=ZBND)
(6=EXTEQ
Monitors the RS 485 port on the DIA
(Not Used)
The 1010/2020 will monitor the auxiliary printer's Ready/Busy line
for error conditions. Note: This option should not be de-activated
for external 80-column printers.
Control module state changes will be logged in History and sent
immediately across the network.
Module state changes for modules with the software type ID
NONA will be logged in history and sent immediately across the
network. (NOA Not Used)
For Retro fit applications, into older systems. All Devices to
Australia were after this Date. Always answer YES.
De-activates or activates 99-device LED latching. Always answer
Yes for Australian Standards and answer Yes to more LED's
when asked.*
Data will be transmitted to the printer under Printer Error
conditions (Paper Out or Printer Off Line generates an error
condition under which data may be lost).
(Not Used)
The 1010/2020 monitors the primary printer's Rx line for error
conditions. This option inhibits the generation of a fault message
for Paper Out or Printer Off Line.