1010/2020 I
A
NSTALLATION
ND
The format for an equation is shown below, where the operators are OR, AND, NOT, XZONE, DEL,
SDEL, and TIM; and the operand's are groupings of initiating devices and/or software zones, as
well as information specific to the format of individual operators.
Examples:
Operator
OR
AND
NOT
XZONE
DEL
SDEL
TIM
All of the operator formats above are explained in detail on the following pages.
Control-By-Event Programming Constraints
•
There can only be one DEL or SDEL operator in a control-by-event equation, not both.
•
If there is no duration time field in a DEL or SDEL, the equation will always be activated.
•
The maximum value of DELAY TIME + DURATION TIME is 255:59:59.
•
If either the day, month or year field is omitted, that field is assumed to be all allowable values of
the field omitted. Example: 12--00 is equivalent to any day in December 2000.
•
The HH.MM field for START TIME and STOP TIME uses military time.
•
The HH.MM field for STOP TIME must be greater than the START TIME.
•
The maximum value of START TIME or STOP TIME is 24:00.
P
M
ROGRAMMING
ANUAL
(- - - - Operand's - - - -)
(Z9 Z15 Z23)
(L1D1 Z3 L1D35 L1D72)
(Z23)
(Z23)
(HH.MM.SS HH.MM.SS (L1M1))
(HH.MM.SS (Z1))
(SU MO TU WE TR FR SA HH.MM HH.MM)