Option 1 from the Main Programming menu allows the programmer to change the programming of
system-wide functions such as Alarm Verification of detectors, enabling Rapid Polling, and enabling
supervision of peripheral equipment in the system, Additional system parameters, such as the
number of Loops, Annunciators and ISIB in the system. Loops can also be changed in Partial
System Programming.
After selecting option 1 from the Main Programming menu, the display will show the Partial System
Programming submenu:
PRESS.1=INST, 2=STY, 3=TDLY, 4=AVPS, 5=ZBND, 6=EXTEQ, 7=LOCP, 8=ISIB, 9=PARM...
The Partial System Programming submenu has nine options, where:
Option
Description
1=INST
Installation – Installation or removal of the Loop Interface Boards from memory.
2=STY
Style - Changing (in memory) loops wiring style 6 or 4.
3=TDLY
Time Delays - Setting the time delays for Alarm Verification, Bell cutout etc.
4=AVPS
Not Used in Australia.
5=ZBND
Zone Boundary - Setting the zone boundary for the software memory map.
6=EXTEQ
External Equipment - Changing the external equipment options, such as electrical
supervision of the Graphics Monitor.
7=LOCP
Local Parameters - Setting local parameters, of Loop devices, and Loop local
mode.
8=ISIB
Intelligent Serial Interface Board - Installation or removal of the Intelligent Serial
Interface Board (SIB-2048A or SIB-NET) or Annunciator modules, Also used for
setting ACS port for Upload/Download with Verifire.
9=PARM
Additional System Parameters – Selection of additional system parameters such
as the detector day/night sensitivity settings, rapid polling, etc.
0=CONT
Continued .......
Subsequent option is 1=IDO, "International Display Option"
Notes
When removing loop interface boards, all installed points on the affected LIBs are automatically
removed upon cycling power to the system. Programming information for installed points can be
stored in a Verifire™ database prior to removal of the LIB. Use of the Verifire™ application for the
reprogramming of previously removed points is highly recommended.
When removing Annunciator modules, all installed points on the affected Annunciators must be
removed first for proper system operation.
P
ROGRAMMING
C
© 2000, N
OPYRIGHT
1010/2020 I
I
P
L
OTIFIER
NERTIA
TY
TD
A
P
NSTALLATION
ND
ROGRAMMING
M
ANUAL

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2020

Table of Contents