1010/2020 I
A
NSTALLATION
ND
Example: Programming Software Zones
Software Zone 13 programmed as a forward zone to activate two other software zones (Z15 and
Z29), and also mapped to Annunciator module address "02" point "05".
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT INSTALL
(BCKSPC TO ABORT)
ENTER TYPE ID
ENTER CONTROL-BY-EVENT
ENTER 20 CHARACTER CUSTOM LABEL
DO YOU WANT THIS POINT MAPPED TO AN ANNUNCIATOR?
(Y=YES,N=NO)
ENTER AXXPYY FOR ANNUNCIATOR POINT MAPPING
Reverse zones on a 1010/2020 system with NOTI•FIRE•NET can be programmed with both CBE
and CCBE *equations. Below is an example of Zone 220 programmed as a reverse zone to
activate once N8 Z1 goes into alarm.
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT INSTALL
(BCKSPC TO ABORT)
ENTER TYPE ID
ENTER CONTROL-BY-EVENT
ENTER COOPERATIVE CONTROL-BY-EVENT
ENTER 20 CHARACTER CUSTOM LABEL
DO YOU WANT THIS POINT MAPPED TO AN ANNUNCIATOR?
(Y=YES, N=NO).
P
M
ROGRAMMING
ANUAL
C
OPYRIGHT
© 2000, N
I
P
OTIFIER
NERTIA
TY
Z13
FZON
(Z15 Z29)
FIRST FLOOR
Y
A2P5
Z220
RZON
()
OR(N8Z1)