* Default Latching (Not recommended)
• Maximum of six devices can be latched at once (five modules maximum).
• Detectors have priority over modules. After six devices have been latched, detectors that
come into alarm will assume LED-latch priority over previously latched module LEDs.
• Under secondary (DC) power, only intelligent detectors (including DHX-501 Duct
Detectors) will be latched.
• Software Type I.D SCON will never latch under Default Latching.
* Optional Latching for More Devices (recommended)
• The control panel will latch up to 99 devices, subject to the limitations outlined below.
• Under primary (AC) power, 99 devices can be latched.
• Detectors have priority over modules. After 99 devices have been latched, detectors that
come into alarm will assume LED-latch priority over previously latched module LEDs.
• Under secondary (DC) power, only intelligent detectors (including DHX-501 Duct
Detectors) will be latched.
L
P
OCAL
ARAMETERS
Option 7 allows the changing of optional features, as Follows:
Piezo for Programming
LIB local mode parameters
Modify NFPA Listing
Battery Programming
Battery Capacity
Battery Standby Time
24 hr High rate charge
Event Reminder
Device Blink
Pre-alarm Function
Note: With pre-alarm activated, the 80% condition must be present for at least a 60 second period
and will indicate a "PRE-ALARM ALERT" message on the Panel after that period. With pre-
alarm de-activated the 80% condition must be present for at least a 26-hour period and will
indicate a "MAINTENANCE REQ" message on the FACP after that period.
(7=LOCP)
Allows you to isolate the piezo whilst programming.
Allows the Loop to maintain operational status if CPU fails.
This Option not used in Australia.
Change the type of battery used (Lead Acid or Nicad).
When Increasing or decreasing the battery capacity.
Change the Duration of Standby time.
Activate or de-activate charge rate.
If activated the piezo will sound every 12-14 seconds when an
acknowledged fault is present on the display.
If activated, the detectors will blink when polled.
If active, the detectors will activate a pre-alarm status when the
obscuration level exceeds 80% of alarm level.