For Cross Zone operation, the XZONE counting operator may be used.
Equation:
XZONE(Z23)
IF ANY combination of two or more initiating
devices (L1D1, L1D2, L1D3, L1D4)
that have been programmed (Control-By-Event)
to this software zone (Z23) come into alarm,
THEN this control module will be activated.
DEL
Operator:
For delayed operation, the DEL operator is used.
Equation:
DEL(HH.MM.SS HH.MM.SS (Z1))
Example:
L1M3 activates Forward Activating Zone 223 (Z223).
L1M2 CBE is: DEL(00.00.30 00.01.30 (Z223))
IF Z223 has been active for 30 seconds
THEN L1M2 will become active. L1M2 will stay active
for 1 minute and 30 seconds provided that Zone Z223
remains active.
Time line
0:00
NOTES
The entire DEL equation consumes at least 11 bytes (including a 3-byte internal equation). The
internal equation can be a complex equation many bytes in size.
If a delay of zero is entered (00.00.00), the equation will evaluate true as soon as the internal
equation evaluates true and will remain that way for the specified duration, unless the internal
equation becomes false.
If no duration is specified, then the device will not be deactivated until a reset occurs or the internal
equation evaluates false.
P
M
ROGRAMMING
ANUAL
0:30
1:00
+————+————+————+————+————+
Z223
L1M2
active active
C
OPYRIGHT
1:30
2:00
L1M2
inactive
© 2000, N
I
P
OTIFIER
NERTIA
TY
2:30
L
TD
P
57
AGE

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Notifier 1010

This manual is also suitable for:

2020

Table of Contents