CPU 1010/2020 General Isolate and General Fault Relays
P
S
OWER
UPPLY
Secondary Power
27.6 V DC, supervised and power-limited.
Fast charge = 2 amps,
Trickle charge = 20 mA.
Active
Neutral
Earth
Circuit Breaker
and Fuse are
by- passed for
use in Australia
JP1: When employing an NR45-24/E or CHG-120,
Remote Battery Charger, JP1 must be cut.
P
M
ROGRAMMING
ANUAL
T
ERMINATIONS
Battery
C
OPYRIGHT
+ -
Resettable Power
24V DC (20.4-26.4, 200 mV ripple), 1 amp
maximum. Filtered and resettable. Power-limited.
+ -
+ -
Non Resettable Power
Power-limited, filtered, non-resettable, 3 amps (in alarm)
maximum.
Terminals 3 and 4) to a resettable, 2-amp maximum circuit.
This output can also be used to power ACS series
Annunciators (do not cut JP5).
MPM-2 Voltmeter/Ammeter Connector
© 2000, N
I
P
OTIFIER
NERTIA
JP5 may be cut to convert this power (TB3
Cut R27 to disable Earth Fault
Detection.
LED Indicators
Earth Fault
Battery Fail
AC Power Fail
NiCad High Charge Rate
JP5: Cut to make notification
appliance power on TB3
Terminals 3 and 4 a resettable 2-
amp maximum circuit.
JP2: must be cut otherwise a
short on the 24vdc
(Terminals 3 and 4) would register
incorrectly as a loss of primary
(AC) power.