Programming - Notifier HS-NCM Installation Documentation

High-speed network communications module
Table of Contents

Advertisement

4 The Network Communications Module for Wire/Fiber
HS-NCM-WSF)
Supports twisted-pair wire and fiber-optic medium.
NFPA Style 4 (Class B) or Style 7 (Class A) operation.
Allows wire and fiber-optic nodes to communicate as one
network.
Fiber type:
• 62.5/125 micrometers (multi-mode, 10 dB limit)
• 50/125 micrometers (multi-mode, 6.5 dB limit)
• 9/125 micrometers (single-mode, 30 dB limit)
Wavelength (1): 1310 nanometers.
Fiber Connectors: LC style.
Wire Connectors: Pluggable terminal wiring with strain
relief.
Data is regenerated at each node.
Two network ports to allow simultaneous connection of up
to two fire alarm control panels and a programming
computer.
Enables software and database upload/download over High-Speed Noti•Fire•Net.
Port A and Port B assignment for the wire and fiber connections are set through VeriFire Tools. Refer to the
VeriFire™ Tools CD on-line help file.
NOTE: When referring to fiber-optic cables, the term "MF" indicates a multi-mode fiber and the term "SF"
indicates a single-mode fiber.
4
Wire
Connection
Ground Fault
Detection
Switches
S1=CH. A
S2=N/A
Figure 3 HS-NCM-WSF/WMF
HS-NCM Installation Document — P/N 54014:B2 04/25/2014
(HS-NCM-WMF,
Fiber
Connection
USB
Connections
NUP
Ports
External
Power
Connection

Hide quick links:

Advertisement