Mitsubishi Electric EZMotion-NC E68 Series Operation Manual page 420

Table of Contents

Advertisement

(Note 6) Automatic initialization cannot be started if one of the following event occurs. An attempt to
start it encounters the message "T01 CAN'T CYCLE ST".
• Data has not been specified for "#0 INIT. SET" parameter.
• Invalid data has been specified for the "#2 ZERO" parameter.
• Data has not been specified for "#2055 pushf" of the [ABS. POSI PARAM] screen.
• "Z71 DETECTOR ERROR 0005" has occurred.
Invalid data for the "#2 ZERO" parameter indicates that the relationship between "#2
ZERO" and zero return parameter "#2037 G53ofs" is inadequate. That is, if the former is
smaller than the latter, the machine end stopper would be located between the zero point of
the basic machine coordinate and machine zero point; this disables automatic initialization.
If the former is 0, the direction of the machine end stopper is unpredictable; this also
disables automatic initialization. See the figure below.
Zero point of basic machine
coordinate
"#2 ZERO"
Zero return cannot be performed because the machine zero
point is located far beyond the machine end stopper when it is
seen from the zero point of the basic machine coordinate.
Explanation of causes that disable automatic initialization
Machine end stopper
(Mechanical basic
position)
Zero-return parameter
"#2037 G53ofs"
III-21
4. Absolute Position Detection System
4.3 Starting up Absolute Position Detection System
Reference
point
If 0 is specified for "#2 ZERO", the
zero point of the basic machine
coordinate is located on the
machine end stopper. The direction
in which the axis is to be moved is
thus unpredictable.
Machine end
stopper
(Mechanical basic
position)
Zero point of basic machine
coordinate