Device Monitor - Mitsubishi Electric FX5 User Manual

Melsec iq-f series, ethernet communication
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Device Monitor

The value of the device specified on the "Device Batch Monitor" screen or "Watch" screen is displayed.
Device Batch Monitor
On the "Device Batch Monitor", the specified device or buffer memory can be monitored in a batch.
■Operations for batch monitor of devices
1.
Select the device to be monitored, and input the first device number.
2.
When monitoring a bit device, select the order. When monitoring a word device, select the Data Type, Display Format,
Display Unit Format (Word/Word Multi-Point) and Order
*1 Only when Display Unit Format is "Word Multi-Point".
■Operations for batch monitor of buffer memory
1.
Select the module No. of the intelligent function module to be monitored, and input the start buffer memory address.
2.
Select the Data Type and Display Format.
■Compatible devices
All devices, excluding labels, can be monitored. However, a device that has a modified index, a word device bit specification,
and bit device digit specification cannot be monitored. (MELSEC iQ-F FX5 User's Manual (Application))
■Changing the current value
Refer toPage 127 Device Test
The device being monitored is automatically updated at the update interval set in the common menu.
Automatic update is enabled from the point that the device is specified. When the device is changed, the
automatic update starts from the point that the device is changed.
*1
.
10 WEB SERVER FUNCTION
10.3 Screen
10
125