Setting Method - Mitsubishi Electric FX5 User Manual

Melsec iq-f series, ethernet communication
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

5.2

Setting Method

The following shows the configuration for communication by SLMP.
Navigation window[Parameter][FX5UCPU][Module Parameter][Ethernet Port][Basic Settings][Own Node
Settings]
1.
Under "Own Node Settings", set "IP Address" setting and "Communication Data Code".
2.
Configure the connection for the SLMP connection.
Navigation window[Parameter][FX5UCPU][Module Parameter][Ethernet Port][Basic Settings][External
Device Configuration][Detailed Setting][Ethernet Configuration (Built-in Ethernet Port)] screen
3.
Drag and drop "SLMP Connection Module" under "Module List" to the left side of the screen. Select protocol (TCP or
UDP) that matches the other device in "Protocol". Set the own station port number (setting range: 1 to 5549, 5569 to
65534) for the "Port No.". Do not specify 5550 to 5568 because these ports are used by the system.
5 SLMP FUNCTION
35
5.2 Setting Method
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents