Analog Unit/Board Specifications; Analog Input Unit (Na0Ax06-Mr); Specifications; Names - Fuji Electric MICREX-SX series SPF User Manual

Hide thumbs Also See for MICREX-SX series SPF:
Table of Contents

Advertisement

Section 3 Specifications

3-6 Analog Unit/Board Specifications

3-6-1 Analog input unit (NA0AX06-MR)

(1) Specifications

Item
Type
No. of input channels
Input impedance
Maximum allowable input
Input range
Resolution
Overall accuracy
A/D conversion value
Sampling period
Moving average
External wire connections
Applicable wire size
Status indication
Isolation method
Occupied words
External power supply
Internal current consumption
Dimensions
*1 The overall accuracy is the specification for when noise described in "Electrical service conditions" is not applied.
If noise is applied, the overall accuracy may exceed the above specification.

(2) Names

Terminal block
Expansion connector (IN)
Status indication LED
* For the detailed specifications of and how to use the analog input unit (Type: NA0AX06-MR), refer to the user's manual "Analog
Unit (FEH527)."
Specification
NA0AX06-MR
6 channels
Voltage: 63.2 kW, Current: 250 W
Voltage: ±15V, Current: 30mA
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
12 bits or 14 bits (Set for individual channels by the program loader.)
±1% *1
INT type
Synchronized with the scan of the main unit.
1 to 16 times (Set for individual channels by the program loader.)
8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
AWG#22-18 * Be sure to use shielded twisted pair cables.
5V power supply display, ON when normal (red)
Not isolated
6 words
24V DC, 53mA *Wiring length: 10m or less
5V DC, 25mA
40 (W) x 90 (H) x 80 (D) (mm)