Calculation Of Current Consumption; Suppliable Current; Current Consumption Of Main Unit - Fuji Electric MICREX-SX series SPF User Manual

Hide thumbs Also See for MICREX-SX series SPF:
Table of Contents

Advertisement

Section 2 System Configuration

2-1-2 Calculation of current consumption

(1) Suppliable current

Type
Main unit
Expansion unit with
power supply
Expansion power supply
Notes:
1) When using an AC power supply type unit at a power supply voltage of 120V AC or less, the total of the internal 24V DC
and externally supplied 24V DC becomes 575mA.

(2) Current consumption of main unit

Type
Advance main unit
Basic main unit
NA0Poooo-ooC
NA0E24T-31
NA0E24R-34
NA0S-2 / NA0S-4
NA0PB14R-34C
NA0PB24R-34C
NA0PB32R-34C
NA0PB60R-34C
NA0PA14T-34C
NA0PA24T-ooC
NA0PA32T-ooC
NA0PA40T-ooC
NA0PA60T-ooC
Internal 5V DC
Internal 24V DC
1000mA
400mA (Note 1)
948mA
350mA
948mA
Total 337mA
400mA
250mA
Internal 5V DC
Internal 24V DC
360mA
65mA
435mA
85mA
520mA
110mA
555mA
200mA
360mA
65mA
435mA
85mA
520mA
110mA
530mA
125mA
555mA
200mA
2-3
Externally supplied 24V DC
400mA (Note 1)
337mA
250mA
Externally supplied 24V DC
(Note 2)
60mA
105mA
138mA
210mA
60mA
105mA
138mA
156mA
210mA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents