PXV3 MODEL CONFIGURATION
P X V 3
Type of Input
Thermocouple (°C)
Thermocouple (°F)
RTD/Pt100 (°C)
RTD/Pt100 (°F)
4-20mA DC, 1-5V DC
0-20mA DC, 0-5V DC
Control Output 1
Relay contact (reverse action)
Relay contact (direct action)
SSR/SSC driver (reverse action)
SSR/SSC driver (direct action)
Control Output 2
None
Relay contact (reverse action)
Relay contact (direct action)
Alarm Option
None
High/Low alarm (SPST)*
*Available with single output only
Power Supply Option
85-264 VAC
24V AC/DC
PXV3 SPECIFICATIONS
INPUT RANGE TABLE:
________________________________________________________
Input Signal
Input Range
(°C)
________________________________________________________
Thermocouple
J
0~800
K
0~1200
R
0~1600
B
0~1800
S
0~1600
T
-199~200
T
-150~400
E
-199~800
N
0~1300
PL2
0~1300
________________________________________________________
RTD
Pt100
-150~850
________________________________________________________
DC Voltage/
Current
1-5V
Scaling Range: -1999 to 9999
0-5V
4-20mA
0-20mA
________________________________________________________
1
Code
T
R
N
S
B
A
Code
A
B
C
D
Code
Y
A
B
Code
4
5
Code
-
D
Input Range
Remarks
(°F)
32~1472
Cold Junction
32~2192
compensating
32~2912
function built-in
32~3272
32~2912
-328~392
-238~752
-328~1472
32~2372
32~2372
-238~1562
Allowable wiring
resistance 10 ohms
max (per wire)
For current input,
use the 250Ω
Engineering Units
resistor to obtain
1-5V or 0-5V DC
input
CONTROL FUNCTION
(SINGLE OUTPUT)
________________________________________________________
Control action
V
________________________________________________________
Proportional band (P)
________________________________________________________
Integral time (I)
________________________________________________________
Differential time (D)
________________________________________________________
P,I,D = 0: 2-position action
I,D = 0: Proportional action
________________________________________________________
Proportional cycle
________________________________________________________
Hysteresis width
________________________________________________________
Anti-reset wind up
________________________________________________________
Input sampling cycle
________________________________________________________
Control cycle
________________________________________________________
CONTROL FUNCTION
(DUAL OUTPUT) (Heat/Cool Type)
________________________________________________________
Heating Proportional band P x 1/2 (P= 0-999.9%)
________________________________________________________
Cooling Proportional band Heating proportional band
________________________________________________________
Integral time
________________________________________________________
Differential time
________________________________________________________
________________________________________________________
P,I,D= 0: 2-position action (without dead band) for heating and cooling
I,D= 0: Proportional action
________________________________________________________
Proportional cycle
________________________________________________________
Hysteresis width
________________________________________________________
Anti-reset wind-up
________________________________________________________
Overlap/dead band
________________________________________________________
Input sampling cycle
________________________________________________________
Control cycle
________________________________________________________
OUTPUT
________________________________________________________
Relay contact output:
________________________________________________________
SSR driver output:
________________________________________________________
Alarm output/
2nd control output:
________________________________________________________
Alarm:
________________________________________________________
SETTING AND INDICATION
________________________________________________________
Accuracy:
________________________________________________________
________________________________________________________
Setting method:
________________________________________________________
Indicator:
________________________________________________________
3
PID control with auto-tuning
Fuzzy control with auto-tuning
0-999.9%, of full scale (FS), setting in 0.1% steps
0-3200 sec, setting in 1 sec steps
0-999.9 sec, setting in 0.1 sec steps
1-150 sec, setting in 1 sec steps, for relay contact
output and SSR/SSC drive output only
0-50% FS, setting in 1 E.U. (Engineering Unit)
steps, 2-position action only
0-100% FS, setting in 1 E.U. steps, auto-setting
with auto-tuning
0.5 sec
0.5 sec
x Cooling proportional band coefficient
Cooling proportional band coefficient= 0-100
0: 2-position action
0-3200 sec for heating and cooling
0-999.9 sec for heating and cooling
1-150 sec, for relay contact output and SSR/SSC
drive output only
2-position action for heating and cooling: 0.5% FS
2-position action for cooling: 0.5% FS
0-100% FS, setting in 1 E.U. steps, auto setting
with auto-tuning
±50% of heating proportional band
0.5 sec
0.5 sec
SPST 220V AC/30V DC 2A (resistive load)
Mechanical life: 10
7
times (under no load)
Electrical life: 10
5
times (under the rated load)
On-5V DC typ. (5.5V ±1V), 20mA max.
Off-0.5V or less
SPST 220V AC/ 30V DC 2A (resistive load)
Configurable from the front panel keys as
Absolute, Deviation, Zone, or Combination alarms
with or without the hold feature.
± 0.5% of FS ± 1 digit ( ± 1°C for thermocouple)
R T/C: 0-400°C: ±1%FS ± 1 digit ± 1°C
B T/C: 0-500°C: ±5%FS ± 1 digit ± 1°C
3-key operation
4 digit, 7-segment LED (green)