(1) Specifications

Item
Type
No. of output channels
External load resistance
Analog output range
Resolution
Overall accuracy
Data type of digital output value
Output period
External wire connections
Applicable wire size
Status indication
Isolation method
Occupied words
External power supply
Internal current consumption
Dimensions

(2) Names

Terminal block
Expansion connector (IN)
Status indication LED
* For the detailed specifications of and how to use the analog output unit (Type: NA0AY02-MR), refer to the user's manual "Analog
Unit (FEH527)."
Specification
NA0AY02-MR
2 channels
Voltage output: 500 W to 1 MW, Current output: 0 to 500 W or less
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
14 bits
±1%
INT type
Synchronized with the scan of the main unit.
8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
AWG#22-18 * Be sure to use shielded twisted pair cables.
5V power supply display, ON when normal (red)
Not isolated
2 words
24V DC, 90mA *Wiring length: 10m or less
5V DC, 33mA
40 (W) x 90 (H) x 80 (D) (mm)
Expansion connector (OUT)
NA0AY02-MR
Terminal block
3-16
<Signal assignment>