E3M111 Line module "SynoLOOP"

10.1
Overview
10.2
Key data
10.3
Special functions
Siemens Building Technologies
Fire & Security Products
Line module for addressable Synova
I-Bus module with line processor and independent emergency operation proces-
sor
Designed for four loop lines or stub lines
Line inputs protected against over voltage
Card format 100mm x 200mm
I-Bus address is set at programming switch "S3"
Addresses per line
Number of wires
Twisted cable
Line resistance
Line capacitance
Short-circuit proof line
Quiescent current at 24V
Current at supply output
1)
Limitations see document 007836
Terminal block X10 (20 terminals)
- mounted on module chassis
- for the connection of the prefabricated cable to
connection level, or
- for direct connection of the periphery
Card chassis
- mounted on module chassis
Line separator
Upon short circuit the part of the line that malfunctions must be separated from the
rest of the line. This is carried out by line separators integrated in each detector,
manual call point and input/output module. According to EN54, a "simple error"
may not cause the malfunction of more than 32 detectors. After the short circuit the
line automatically reverts to "Normal operating condition".
E3M111 Line module "SynoLOOP"
TM
detectors
1)
...128
2
recommended
1)
...150Ω with 128 detectors
1)
...300nF
yes (automatic detectors, manual call points, input/output mod-
ules with line separator)
210mA with 512 detectors
(50mA without detectors + 0.31mA per D-Bus user)
....500mA / 18...30VDC (not stabilized)
E3M111
37
007831_a_en_--.doc
03.2004