Connections - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

18.5

Connections

E3G070
Remote
LED
H1
transm. alarm
Remote transm. fault
LED
H2
(Shown in normal operation)
LED
H3
Alarm horn 1,
monitored control line
LED
H4
Alarm horn 2,
monitored control line
Supply output remote transmission
Module chassis ground
+24V
LED
H5
Inputs / outputs
24V 40mA
LED
H6
LED
H7
LED
H8
LED
H9
LED
H10
LED
H11
0V
Plug-in terminals
Supply for
I-Bus modules
F1
Double flat cable header
Data communication
I-Bus modules
1) The indicated polarity at the terminals 5...8 applies to the active state
2) The output X1-9,10 is always monitored
3) Terminate not used horn lines with a 4,75kΩ resistor
Siemens Building Technologies
Fire & Security Products
default connection of
E3G070 at Pos. 38
X1
Terminal block
1
K1
Y12
X12
2
3
K2
Y13
X13
4
F6
+
5
24V
F7
-
6
1)
3)
F8
+
7
24V
F9
-
8
F2
+
9
F3
2)
-
10
(connect to
11
chassis ground)
+
12
F4
Q1/I1
-
13
-
14
Q2/I2
Q3/I3
-
15
-
16
Q4/I4
Q5/I5
-
17
-
18
Q6/I6
Q7/I7
-
19
F5
20
K1
-
1
blue
GND
-
2
blue
5V
+
3
green
24V
+
4
red
ST1
Terminal block X1
1
2
3
4
5
max. 2A
6
7
max. 2A
8
9
to teletransmission unit or to other internal load
10
11
12
13
14
Function output
15
16
17
18
Function input
19
20
from I-Bus module E3C011
to I-Bus module E3M111
from I-Bus module E3C011
to I-Bus module E3M111
E3G070 Control module "Universal"
to remote
transmission equipment
max. 24W (60V 1A)
4.75kΩ
4.75kΩ
Relay / contact must not be outside the
control unit housing
007831_a_en_--.doc
73
03.2004