E3I040 I-Bus/Lon Module - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

E3I040 I-Bus/LON module

11
E3I040 I-Bus/LON module
11.1
Overview
11.2
Application
11.3
Key data
Number of devices per line
LON-Bus:
number of wires
cable type
max. cable length
LON-Bus: connection
Typical current consumption (24V)
Rating supply output (pin 9/10)
1) free topology see page 45
44
Siemens Building Technologies
Fire & Security Products
Converter I-Bus to LON-Bus
Up to 32 LON-Bus devices connectable
With 24V supply output
Selectable ground fault monitoring, detected via E3G070 (for application details
see chapter 6, "Ground fault monitoring")
Board format 100mm x 200mm
I-Bus address is set at programming switch "S3"
Only one module per station possible
Required for all LON applications within FC700A, such as:
LON-I/O p.c.b. K3I110
LON/Mimic Display converter K3I050 with Mimic display drivers K3R072 (or
panels B3R051)
Floor repeater panel B3Q580
Floor repeater panel with control functions B3Q590/595
Terminal block X2 (20 terminals)
- mounted on module chassis
or in H28 housing
- for direct connection of the periphery
Card chassis
- mounted on module chassis
...32
2
twisted (10 twists per m)
standard cable twisted 0,8mm ø unshielded as 'stub line'
same but as 'free topology' 1)
using MICC-cable
using MICC-cable as 'free topology' 1)
using special cable Belden 85102 or 8471
twisted cable necessary
15mA without load on output (pin 9/10)
max. 860mA / 20....29,6V
E3I040
...1000m
.....500m
.....700m
.....300m
...2700m
007831_a_en_--.doc
03.2004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents