Connections - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

9.8

Connections

E3M080
Terminal block
Line 1
Line 2
Line 3
Line 4
unused
Module chassis ground
unused
Line 5
Line 6
Line 7
Line 8
Plug-in terminals
Supply
I-Bus modules
Double flat cable header
Data communication
I-Bus modules
1) Local ground connection
2) To read in technical alarms. Do not mix with detectors on the same line
Siemens Building Technologies
Fire & Security Products
X20
Max. 25 collective detectors
F1
+
1
F2
-
2
F3
+
3
Transzorb 20V
F4
-
4
resistor 1.2kΩ
F5
+
5
F6
-
6
F7
+
7
Transzorb 20V
F8
-
8
9
10
11
(connect to chassis ground)
12
F9
+
13
Transzorb 20V
F10
-
14
F11
+
15
Transzorb 20V
F12
-
16
F13
+
17
Transzorb 20V
F14
-
18
F15
+
19
F16
-
20
K1
-
1
blue
GND
-
2
blue
5V
+
3
green
24V
+
4
red
ST1
Z-Diode
Z-Diode
5.6V
5.6V
Alarm contact
*
or
*
SB3
DC1192
1)
24V
DC
from previous I-Bus modules
to other I-Bus modules
from previous I-Bus modules
to other I-Bus modules
E3M080 Line module "Collective"
Line type11 = Transzorb 20V
*
1 = EOL22 (Ex)
*
Z-Diode
5.6V
*
2)
Ex detectors
EOL22 (Ex)
Explosion hazard area
007831_a_en_--.doc
35