Ground Fault Monitoring (Fm Compliance) - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

6

Ground fault monitoring (FM compliance)

F M
APPROVED
6.1
Modules overview for FM compliant installations
Siemens Building Technologies
Fire & Security Products
Customer sites covered by the American Factory Mutual (FM) insurance company
have special requirements to their fire panels. The basic FM requirement is to safely
monitor and detect ground faults, of all lines leaving the panel.
The FC700A has been technically adjusted to fulfil those requirements.
For FM installations, adhere the FM Approval mark to the control unit housing next to
the type label.
All modules are delivered pre-set with today's functionality, so that when setting up
FM installations only, minor adjustments are necessary on some of the modules ac-
cording to the following description.
Modules with part numbers are suitable for FM installations.
Module
B3Q700
Control console
E3G070
Control module "universal"
E3I040
I-Bus/LON module
K3I110
LON-I/O p.c.b.
E3L020
Control module "I/O"
E3G060
Control module "monitored"
E3H020
C-Bus Gateway
Remarks
With an E3L030 board installed, the system is not FM compliant.
Please verify part of used modules and check jumper settings as described in the following scheme.
Ground fault monitoring (FM compliance)
Part number
Jumper setting
A5Q00004759
yes
546661
yes
499310
yes
528854
yes
546645
no
542539
no
no
546658
21
007831_a_en_--.doc
03.2004