NOTES:
1. Compatible wire size:
14 - 18 AWG
2. No EOLR required. S1-1, S1-2
has to be on the ON position
if the SSD-C is at the end of
the Style 4 or Style 7 network.
3. Use twisted pair or twisted
shielded pair
4. Terminate shield at one end
only.
5. Power Limited to NFPA 70
per NEC 760.
6. All wiring is power limited
and supervised.
Siemens Building Technologies
Fire Safety
Detail View - Properties
Disconnect BATTERY and AC prior to working on equipment.
PAIR B (STYLE 7 ONLY)
PAIR A (STYLE 4, STYLE 7)
SSD-C
24VDC (POWER LIMITED)
Figure 5
Typical SSD-C Connection To The FireFinder XLS
SIEMENS
NIC-C
FireFInder XLS ENCLOSURE
7
Physical View
PMI/CPC
PSC-12
P/N 315-048733-3