Important Components - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

E3I040 I-Bus/LON module
11.5

Important components

Jumper "X30":
Ground fault monitoring 'LON-Bus''
out' = inactive (factory setting)
'in' = active
(for application details see
chapter Ground fault monitoring)
Programming switch "S3":
"I-Bus address" setting
(see chapter Programming switch)
Flat cable header "ST1" (26-pin):
I-Bus
LED "H1":
lights up during data transfer
between E3I040 and LON-Bus
LED "H2":
lights up during data transfer
between I-Bus and E3I040
Plug-in terminals "K1":
Supply to modules "I-Bus"
11.6
Programming switch "S3"
46
Siemens Building Technologies
Fire & Security Products
S1
S3
ASIC
1
ST1
ON
F1
H1
µP
H2
1
K1
4
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch "S3". Maximum 16
I-Bus devices.
Function / I-Bus address
No.
0
Module out of commission (not used)
1
I-Bus device number
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
R60
X30
H3
LON
E3I040
C
µ
EPROM
RAM
Key "S1": Service key
(not used)
Fuse
F1
2A/T for output 24VDC
Fuse with high breaking capacity
(sand-filled)
Programming switch S3
S3-1
off
1
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
Resistor "R60" 100 :
EOL (LON-Bus)
to be replaced by resistor
of 50 , if LON-Bus is
connected as free topology
Test-LED "H3":
inactive -> Normal operation
lit or blinking-> EPROM
missing or faulty
S3-2
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on
007831_a_en_--.doc
S3-6
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
03.2004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents