K3I110 Lon I/O P.c.b - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

K3I110 LON I/O p.c.b.

25
K3I110 LON I/O p.c.b.
25.1
Overview
25.2
Application
25.3
Key data
25.4
Wiring principle
LON-Bus
E3I040
24V
DC
16 programmable monitored control inputs
96
Siemens Building Technologies
Fire & Security Products
In-/output card with 16 programmable control in-/outputs
LON-Bus device
Max. 32 devices
Selectable ground fault monitoring, detected via E3G070 (for application details
see chapter 6)
Card format 100mm x 200mm
Equipped with mounting plate
The card communicates (LON-Bus) via converter module E3I040 (LON-/I-Bus)
with the control unit.
Output contacts, NO
Ratings relay contacts
Inputs
Operating voltage
Current consumption at
* all relay activated incl. service LED
K1
K3I110
X31
X38
X56
16 programmable control outputs
Outputs are galvanically isolated, not supervised on open circuit,
short circuit or ground fault
max. 1A / 30VDC
supervised on open circuit, short circuit, deviation and ground
fault
9...45VDC
24V
min. 24mA / max. 184mA *
9V
min. 53mA / max. 218mA *
45V
min. 19mA / max. 171mA *
per activated relay (at 24V) 10mA (without LED 9,2mA)
per input with closed contact max. 0,5mA
max. length of LON-Bus 1000m
X63
24V
max. 30V /1A
K3I050
B3Q580
Data bus
DC
007831_a_en_--.doc
B3Q590/
595
03.2004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents