E3G060 Control module "Monitored"

17.1
Overview
17.2
Application
17.3
Key data
Siemens Building Technologies
Fire & Security Products
Control module for monitored alarm devices
6 monitored control lines 24V 2A with EMI and over voltage protection
Individual allocation of control lines via maintenance PC (SWE700A)
It is possible to specify separately whether or not each line must be activated in
"Emergency alarm" mode (programming switch "S6")
Drive horns by internal or external oscillator (intermitted Horn output)
Max. 8 x E3G060 cards per system (synchronized over plug-in terminal K2)
Ground fault monitoring, detected via E3G070 (for application details see chap-
ter 6)
Card format 100mm x 200mm
I-Bus address is set at programming switch "S3"
The E3G060 module is required in systems with more than 2 monitored control
lines for alarm / or similar equipment
The current on one control line may not exceed 2A; however, the total current for
all 6 control lines may not exceed 4A (internal supply K1).
Control outputs
number
max. load
termination resistor
Quiescent current at 24V
1)
output at same voltage range as from the external supply (K3)
Terminal block X1 (20 terminals)
- mounted on module chassis
- for the connection of the prefabricated cable to
connection level, or
- for direct connection of the periphery
Card chassis
- mounted on module chassis
E3G060 Control module "Monitored"
6
2A each at 20.. 30V; total 4A (internal supply, K1)
1)
2A each at 24V
; total 12A (external supply, K3)
4.75kΩ
25mA (no control line active)