Wiring Principle - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

B3R051 Parallel indicator panel
21.4

Wiring principle

K3I050
K1
ST2
or
B3Q700
K7
ST4
F12A100: 0.4m
F12A470: 1.5m
K3I050
K1
ST2
or
B3Q700
K7
ST4
Adapter
Z3I350
82
Siemens Building Technologies
Fire & Security Products
Control terminal and parallel indicator panel in immediate vicinity
First 24 display fields
B3R051
Equipment 1
K1
ST1
Data bus
Parallel indicator panel separate from control terminal
First 24 display fields
Parallel derivation
permissible
Data bus
max. 1000m
Note:
max. 24 units B3R051 or K3R072 (also mixed) possible with max. 8 different addresses
remove resistor array (see page 83) except on one unit
Second 24 display fields
ST2
Data bus
24V supply line
B3R051
Equipment 1
K1
K2
ST2
Data bus
24V supply line
B3R051
Equipment 2
K1
ST1
ST2
Second 24 display fields
B3R051
Equipment 2
K1
ST1
ST2
007831_a_en_--.doc