K3R072 Mimic Display Board - Siemens FC700A Hardware Description

Fire detection system
Table of Contents

Advertisement

22

K3R072 Mimic Display board

22.1
Overview
22.2
Application
22.3
Key data
Synoptic display
Short-circuit proof in-/outputs
panel housing
only for
K3R072
K3R072
Z3I520
Siemens Building Technologies
Fire & Security Products
Option to control console B3Q700, or to LON/Mimic Display converter K3I050
2x24 outputs for LED activation for Mimic Display panels, or not monitored relay
contacts (K3G060)
2 control outputs for local 'Buzzer' and 'LED operation'
2 inputs for 'Switch-off buzzer' und 'Lamp test'
The lamp test is integrated in menu function B3Q700
Individual allocation of the individual outputs
Max. 24 units, however max. 8 addresses
Communication is via a special serial bus
Line and device not monitored
The Mimic Display board is built into the mimic panel housing.
Connection to LED via flat cable F50F410 (50-wire, 24 red LEDs, cable length
1m, must be ordered separately)
The relay card K3G060 can be connected instead of LEDs
Line length data bus B3Q700 → K3R072 max. 1000m
Connection line
Data bus:
via flat cable or 6-wire cable
Supply 24V:
via 3-wire cable
Operating voltage
Current consumption
at 24V
at 9V
at 45V
inside
housing application
max. permissible length
of the data bus 1000m
LED 1....24
wires 49+50 for 'LED operation'
LED 25....48
wires 49+50 unused
Key 'Switch-off buzzer'
Key 'Lamp test'
Buzzer
9...45VDC
quiescent 40mA
max. 140mA
quiescent 80mA
max. 330mA
quiescent 30mA
max. 90mA
These in-/outputs can be in
parallel with other K3R072
if located in same cabinet
K3R072 Mimic Display board
B3Q700