B3Q580 Floor repeater panel and B3Q590/B3Q595 Floor repeater panel with control functions
26.3

Mechanical design

B3Q580
Cover frame
Slide-in inscription strips
26.4
Important components B3Q580, B3Q590, B3Q595
Potentiometer "R28":
LCD contrast adjustment
LED "H1":
inactive -> normal operation
lit or flash -> EPROM defective or missing
Key "S2": Service key
(unused)
Plug-in connector "ST1":
backlight
Fuse "F1":
1A/T for supply input 9..45VDC
Resistor 'R1' 100 : Ω
EOL (LON-Bus)
at application stubline:
to be remove resistor, if B3Q580
/590/595 is not the last device on
the LON-Bus (see E3I040 chapter
Principle wiring)
Siemens Building Technologies
Fire & Security Products
Plastic housing H23G230
Display
Cover frame
4 Mounting screws
Slide-in inscription strips
B3Q580
LON
RAM
µ
EPROM
S2
ST1
R1
F1
K1
1
Plug-in terminals "K1":
Module supply and LON-Bus
for operating access:
- B3Q590: Nordic fire brigade key switch
- B3Q595: KABA fire brigade key switch
B3Q590/595
Programming switch "S3":
"LON-Bus address" setting
(see chapter Programming switch)
Programmierschalter "S4":
S4-1= IB-Mode (ON: Summer aus)
R28
S4-2= nicht benutzt
P
H1
ON
ON
S4
1
1
S3
6
ST1
K1
yellow LEDS in exchange
by green LEDS
Nordic key or KABA key
B3Q590
B3Q595
LON
RAM
µ
P
H1
ON
EPROM
S4
S2
1
S3
K2
R1
F1
1
6
1
Plug-in terminals "K2":
Programming inputs for
indication fields (LEDs)
007831_a_en_--.doc
R28