en | System and Consumer Options
The MAINS indicator stops flashing when the AC MAINS supply is restored longer than 2 min.
An AC Loss Restore Report is transmitted to the base station receiver after the AC MAINS
supply is restored continuously for more than 2 min regardless of whether this option is
selected.
2 – Ignore AC Fail
If this option is selected, the MAINS indicator does not flash and the codepad does not beep
every minute when the AC MAINS is disconnected from the control panel. If you want a
programmable output to operate when the AC MAINS fails, use Output Event Type 1,4 AC Fail.
An AC Loss report is transmitted to the base station receiver regardless of whether this option
is selected.
4 – Zone Pulse Count Handover
If this option is selected, any zone pulse count readings are handed over and accumulate to
any zone that is activated during the same arming cycle. Zone pulse count handover only
operates with zone pulse count time options 8 to 15. Refer to Zone Pulse Count, page 99 and
Zone Pulse Count Time, page 100 for more information.
Notice!
24-Hour Zones cannot receive any handover pulses from other zones. 24-Hour Zones can hand
over pulses to other zones.
8 – Handover Delay to Be Sequential
If this option is selected, handover delay is sequential (that is, in zone numerical order from
lowest to highest). If the sequence is broken before the Entry Time expires, an alarm occurs. If
this option is not selected, handover delay follows the entry path if a Delay Zone is activated
first. Refer to Zone Types, page 97 for more information about Handover Zones and Delay
Zones.
Example:
Program zone 1 as Delay Zone and zone 2 and 3 as Handover Zone. When the Handover Delay
to Be Sequential is selected and the zone 1 is activated:
If the zone 3 is activated first and the zone 2 is activated followed before the Entry Time of
zone 1 expires, zone 3 alarms immediately, while zone 1 and zone 2 alarm after the Entry Time
expired because zone 3 is higher than zone 2 in numerical order.
If the zone 2 is activated first and the zone 3 is activated followed before the Entry Time of
zone 1 expires, zone 1 and zone 3 alarm after the Entry Time expired because the zones are
activated in sequential.
18.4

System Options 4

Item
System Options 4
1 – Panel To Power Up Disarmed
If this option is selected, the control panel powers up in the disarmed state when the battery
and AC MAINS are reconnected after the system is powered down.
If this option is not selected, the system is always powered up armed in AWAY Mode.
2 – Arm/Disarm Tracking on Power Up
2017.10 | 03 | F.01U.298.026
Location
Option
0495
1 = Panel to power up disarmed (if power
reset)
2 = Arm/disarm tracking on power up
4 = Onboard tamper trigger alarm
8 = Reserved
Installation Guide
Control Panel
Default
New
6