Control Panel
Location 379 determines the number of times the sirens can be activated before lockout
options take effect. This location has no effect unless you program at least one zone for
lockout siren. Refer to Zone Options 1, page 100 for more information.
Only alarms activated from zone inputs can increment the Swinger Shutdown Counter. Alarms
such as Codepad Panic, Access Denied, and other system alarms do not affect the Swinger
Shutdown Count.
Lockout Siren is separate for each zone, If a zone's siren is locked out, another zone's siren
can still be activated.
Example
Zone1 and 2 are programmed for Lockout Siren with a Swinger Shutdown Count of 2. If Zone
1 activates an alarm, the Swinger Shutdown Count is incremented by one after the end of
Siren Run Time from 0 to a swinger shutdown count of 1.
After the Siren Run Time is reset from the previous alarm, Zone 2 activates an alarm and
activates the sirens. After the sirens are reset, the swinger shutdown count for Zone 2 is
incremented to 1 and the swinger shutdown count for Zone1 is still 1.
If Zone 1 activates an alarm again after the sirens are reset from Zone 2, the Swinger
Shutdown Count for Zone 1 is incremented to 2, which locks out Zone 1 only from sounding
the sirens until the system is reset, armed or disarmed.
At this point, Zone 1's Swinger Shutdown Count for Sirens is reset to 0.
13.5

Swinger Shutdown Count for Report

Item
Swinger Shutdown Count
For Report
Location 380 determines the number of times the zone alarm report can be activated before
lockout options take effect. This location has no effect unless you program at least one zone
for lockout report. Refer to Zone Options 1, page 100 for more information.
Only alarms activated from zone inputs can increment the Swinger Shutdown Counter. Alarms
such as Codepad Panic, Code Retries, and other system alarms do not affect the Swinger
Shutdown Count.
Lockout Report is separate for each zone. If a zone's report is locked out, another zone's
report can still be activated. Each zone has a standalone Swinger Shutdown Count for Report.
This counter increases by 1 when a zone reports a new alarm or tamper event.
Use Location 492 to set smart lockout. When a zone report is locked out, if smart lockout is
enabled, lockout events on this zone are not reported if no alarm is sounding. If an alarm is
ongoing, events are reported as configured.
Notice!
If Lockout Report is enabled for any zone, the last restore signal is not transmitted until the
system is disarmed.
Example
Zones 1 and 2 are programmed for lockout report with a Swinger Shutdown Count of 6. If
Zone 1 activates an alarm, the Swinger Shutdown Count increments to 1 when the control
panel sends the report.
If Zone 1 reactivates the report, the Swinger Shutdown Count is incremented to 2. If Zone 1
reactivates the report three more times, the Swinger Shutdown Count is 5.
Bosch Security Systems, Inc.
Location
Option
0380
1 – 15 = Number of times report operates
until lockout
Installation Guide
Zone Information | en
Default
New
6
2017.10 | 03 | F.01U.298.026