Bosch Solution 2000 Installation Manual page 127

Hide thumbs Also See for Solution 2000:
Table of Contents

Advertisement

Control Panel
This output operates when a 24-Hour Fire Zone or codepad fire alarm is activated and is reset
when a valid user code is entered in system disarmed state or before the siren time expires in
system armed state.
2,7 Fire Alarm Verification
This feature is used on some commercial fire control panels to reduce false alarms from
smoke detectors. It is similar to zone pulse count used in some motion detectors. A fire zone
is allotted a pulse count of 3 pulses over a period of 3 min.
If the smoke detector trips, the voltage to the smoke detector is disconnected for 15 sec and
then reapplied. No alarm is registered.
If the unit activates again within 3 min of the first activation, no alarm is registered and the
voltage to the smoke detector is again disconnected for 15 sec and then reapplied.
If a third activation is detected within 3 min of the first activation, (three pulses in 3 min) a
fire alarm is registered. Power to the smoke detector is maintained to facilitate unit
identification through the detector memory.
Connect this output to the negative side of any fire/smoke detector. To configure an output
for this feature, use these settings.
EVENT TYPE – 2,7
POLARITY – 10
TIMEBASE – 2
MULTIPLIER – 15
The zone to which the fire or smoke detector is
connected should be programmed as:
ZONE TYPE – 13
ZONE PULSE COUNT – 3
ZONE PULSE COUNT TIME – 15
2,8 Remote Control 1
This output operates output when using the master code function or A-Link software or
Smartphone App (RSC) to turn remote output 1 on. The output is reset when using the master
code function or A-Link software or Smartphone App (RSC) to manually turn remote output 1
off or automatically turn remote output 1 off when the ON time expires if output polarity is
from 3 to 6 or from 10 to 13.
2,9 Remote Control 2
This output operates output when using the master code function or A-Link software or
Smartphone App (RSC) to turn remote output 2 on. The output is reset when using the master
code function or A-Link software or Smartphone App (RSC) to manually turn remote output 2
off or automatically turn remote output 2 off when the ON time expires if output polarity is
from 3 to 6 or from 10 to 13.
2,10 Remote Control 3
This output operates output when using the master code function or A-Link software or
Smartphone App (RSC) to turn remote output 3 on. The output is reset when using the master
code function or A-Link software or Smartphone App (RSC) to manually turn remote output 3
off or automatically turn remote output 3 off when the ON time expires if output polarity is
from 3 to 6 or from 10 to 13.
2,11 Radio Control Output 1
This output operates when the "1 Point" button (RADION) on the 4-button keyfob is toggled
ON. The output is reset when this button is toggled OFF manually or automatically toggled off
when the ON time expires if output polarity is from 3 to 6 or from 10 to 13.
2,12 Radio Control Output 2
Bosch Security Systems, Inc.
Installation Guide
Programmable Outputs | en
2017.10 | 03 | F.01U.298.026
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solution 3000

Table of Contents