en | System Reporting Information
Each time the system is armed or disarmed, the Code Retries counter is reset. You can
program the counter to a value from 1 to 15. If you want the number of incorrect code
attempts to be unlimited, program a 0 in Location 424. In this case, the Access Denied Report
is never generated and the system does not perform the three actions listed above. This
function works when the system is armed or disarmed.
15.4

System Status Reporting Options

Item
System Status
Reporting Options
Location 427 is set by default to report only to Receiver 1.
15.5

Test Reporting Time

Item
Hour of day (tens digit)
Hour of day (units digit)
Minute of day (tens digit)
Minute of day (units digit)
Repeat interval in days
A Test Report (Contact ID Event Code 601/602) is a specific signal sent to the base station
receiver and is normally used to test the dialing and reporting functions of the control panel.
When programming Test Report options, specify the hour and minute of the day the report is
required, and how often to send the report. Test reports are reported on a daily basis from
every day to every fifteen days. Program the Test Report Time as 34:00 to send reports every
60 minutes.
Example
Set auto test report interval to the 37
34:37. Then the auto test report will be sent at 00:37, 01:37, 02:37, etc.
If you want to send Test Reports once every seven days at 11:35 PM (23:35), program
Locations 428 to 431 as [2 3 3 5] and location 434 as [7].
2017.10 | 03 | F.01U.298.026
Activates the sirens, internal screamers, and strobes connected to the control panel.
Select Option 8 in Location 493 to change this alarm to silent.
Shuts down all codepads connected to the control panel and locks them out for the time
period programmed in Location 478 (refer to Codepad Lockout Time, page 136).
Sends an Access Denied Report (Contact ID Event Code 461) to the base station receiver.
Location
Option
0427
0 = No report required
1 = Report to Receiver 1
2 = Report to Receiver 2
3 = Report to Receiver 3
4 = Report to Receiver 4
5 = Report to Receiver 1,2,3,4
6 = Report to Receiver 1 (2,3,4 backup)
7 = Report to Receiver 1 (2 backup) and
Receiver 3 (4 backup)
Location
0428
0429
0430
0431
0434
Option
0 = Disable
1 – 15 = 1 – 15 days
minute of every hour, the time needs to be set as
th
Installation Guide
Control Panel
Default
New
1
Default
New
0
0
0
0
0