B.4 MEMORY MAPPING
F103
ENUMERATION: CURVE SHAPES
Bitmask
Curve shape
0
IEEE Mod Inv
1
IEEE Very Inv
B
2
IEEE Ext Inv
3
IEC Curve A
4
IEC Curve B
5
IEC Curve C
6
IEC Short Inv
7
IAC Ext Inv
8
IAC Very Inv
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112
ENUMERATION: RS485 BAUD RATES
Bitmask
Value
0
300
1
1200
2
2400
3
4800
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
B-74
Bitmask
Curve shape
9
IAC Inverse
10
IAC Short Inv
11
I2t
12
Definite Time
13
FlexCurve A
14
FlexCurve B
15
FlexCurve C
16
FlexCurve D
Bitmask
Value
Bitmask
4
9600
8
5
19200
9
6
38400
10
7
57600
11
G30 Generator Protection System
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F116
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B,
3 = FlexCurve C
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
F124
ENUMERATION: LIST OF ELEMENTS
Bitmask
Element
0
Phase Instantaneous Overcurrent 1
1
Phase Instantaneous Overcurrent 2
16
Phase Time Overcurrent 1
24
Phase Directional Overcurrent 1
32
Neutral Instantaneous Overcurrent 1
48
Neutral Time Overcurrent 1
56
Neutral Directional Overcurrent 1
57
Neutral Directional Overcurrent 2
60
Negative Sequence Directional Overcurrent 1
61
Negative Sequence Directional Overcurrent 2
64
Ground Instantaneous Overcurrent 1
80
Ground Time Overcurrent 1
86
Restricted Ground Fault 1
Value
87
Restricted Ground Fault 2
115200
88
Restricted Ground Fault 3
14400
89
Restricted Ground Fault 4
28800
101
Change Phase Rotation
33600
120
Negative Sequence Overvoltage 1
125
Generator Unbalance
140
Auxiliary Undervoltage 1
141
Auxiliary Undervoltage 2
144
Phase Undervoltage 1
145
Phase Undervoltage 2
146
Phase Undervoltage 3
148
Auxiliary Overvoltage 1
149
Auxiliary Overvoltage 2
APPENDIX B