GE G30 Instruction Manual page 204

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
Transmitted voltage Vt = (8191/(Vn*2.4)) * V - 4096 =
= (8191/(500000 * 2.4) ) * V - 4096 = 0.0068 * V - 4096
a = 0.0068
Since the step is in increments of 0.001, we round it at:
a = 0.006
b = -4096
Vt = 0.006 * V - 4096
For max voltage 500000V * 2.4 = 1200000V, we transmit
Vt = 0.006 * 1200000 - 4096 = 7200 - 4096 = 3104
PATH: SETTINGS
PRODUCT SETUP
 IEC103 COMMANDS
5
 COMMAND 0
 COMMAND 31
Commands are received as General Command (Type Identification 20). The user can configure which action to perform
when an ASDU command comes.
A list of available mappings is provided on the G30. This includes 64 virtual inputs (see the following table). The ON and
OFF for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN), and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
5-64

COMMUNICATIONS
 COMMAND 0
 COMMAND 1
MESSAGE
 COMMAND 31
MESSAGE
COMMAND 0 FUN:
0
COMMAND 0 INF:
MESSAGE
0
COMMAND 0 ON:
MESSAGE
Off
COMMAND 0 OFF:
MESSAGE
Off
COMMAND 31 FUN:
0
COMMAND 31 INF:
MESSAGE
0
COMMAND 31 ON:
MESSAGE
Off
COMMAND 31 OFF:
MESSAGE
Off
G30 Generator Protection System

IEC60870-5-103
IEC103 COMMANDS
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents