GE G30 Instruction Manual page 533

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 13 of 64)
ADDR
REGISTER NAME
Security (Read/Write)
328B
Administrator Alphanumeric Password Entry
Security (Read/Write Setting)
3295
Supervisor Alphanumeric Password Setting
Security (Read Only)
329F
Supervisor Alphanumeric Password Status
Security (Read/Write)
32A0
Supervisor Alphanumeric Password Entry
Security (Read/Write Setting)
32AA
Engineer Alphanumeric Password Setting
Security (Read Only)
32B4
Engineer Alphanumeric Password Status
Security (Read/Write)
32B5
Engineer Alphanumeric Password Entry
Security (Read/Write Setting)
32BF
Operator Alphanumeric Password Setting
Security (Read Only)
32C9
Operator Alphanumeric Password Status
Security (Read/Write)
32CA
Operator Alphanumeric Password Entry
Security (Read/Write Setting)
32D4
Observer Alphanumeric Password Setting
Security (Read Only)
32DE
Observer Alphanumeric Password Status
Security (Read/Write)
32DF
Observer Alphanumeric Password Entry
Security (Read Only)
32E9
Reserved for password settings of future roles (63 items)
3328
Security Status Indicator
Security (Read/Write Setting)
3329
Session Lockout
332A
Session Lockout Period
332B
Load Factory Defaults
332C
Syslog Server IP Address
332E
Syslog Server Port Number
Security Supervisory (Read/Write Setting)
3331
Device Authentication Enable
3332
Supervisor Role Enable
3333
Lock Relay
3334
Factory Service Mode Enable
3335
Failed Authentication Alarm Enable
3336
Firmware Lock Alarm
3337
Settings Lock Alarm
3338
Bypass Access
333A
Serial Inactivity Timeout
Security Command (Read/Write Command)
3350
Operator Logoff
3351
Engineer Logoff
3352
Administrator Logoff
3353
Clear Security Data
Security Reserved Modbus Registers (Read/Write)
3360
Address 0x3360 reserved for serial login (20 items)
3374
Address 0x3374 reserved for serial logout
GE Multilin
RANGE
---
---
0 to 1
---
---
0 to 1
---
---
0 to 1
---
---
0 to 1
---
0 to 65535
0 to 65535
0 to 99
0 to 9999
0 to 1
0 to 4294967295
1 to 65535
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 3
1 to 9999
0 to 1
0 to 1
0 to 1
0 to 1
0 to 9999
0 to 9999
G30 Generator Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
---
F202
---
---
F202
---
1
F102
---
---
F202
---
---
F202
---
1
F102
---
---
F202
---
---
F202
---
1
F102
---
---
F202
---
---
F202
---
1
F102
---
1
F202
---
1
F001
---
1
F618
---
1
F001
min
1
F001
---
1
F126
---
1
F003
---
1
F001
---
1
F126
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F628
---
1
F001
---
1
F126
---
1
F126
---
1
F126
---
1
F126
---
1
F001
---
1
F001
DEFAULT
(none)
(none)
B
0 (Disabled)
(none)
(none)
0 (Disabled)
(none)
(none)
0 (Disabled)
(none)
(none)
0 (Disabled)
(none)
0
0
3
3
0 (No)
0
514
1 (Yes)
0 (Disabled)
0 (Disabled)
0 (Disabled)
1 (Enabled)
1 (Enabled)
1 (Enabled)
0 (Disabled)
1
0 (No)
0 (No)
0 (No)
0 (No)
3
3
B-21

Advertisement

Table of Contents
loading

Table of Contents