GE G30 Instruction Manual page 557

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 64)
ADDR
REGISTER NAME
7B90
...Repeated for User Programmable Pushbutton 2
7BC0
...Repeated for User Programmable Pushbutton 3
7BF0
...Repeated for User Programmable Pushbutton 4
7C20
...Repeated for User Programmable Pushbutton 5
7C50
...Repeated for User Programmable Pushbutton 6
7C80
...Repeated for User Programmable Pushbutton 7
7CB0
...Repeated for User Programmable Pushbutton 8
7DE0
...Repeated for User Programmable Pushbutton 9
7D10
...Repeated for User Programmable Pushbutton 10
7D40
...Repeated for User Programmable Pushbutton 11
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
7DD0
...Repeated for User Programmable Pushbutton 14
7E00
...Repeated for User Programmable Pushbutton 15
7E30
...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F07
Neutral Overvoltage 1 Target
7F08
Neutral Overvoltage 1 Events
7F09
Neutral Overvoltage 1 Curves
7F0A
Reserved (7 items)
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting (2 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F68
Auxiliary Undervoltage 1 Target
7F69
Auxiliary Undervoltage 1 Events
7F6A
Reserved (7 items)
7F71
...Repeated for Auxiliary Undervoltage 2
Auxiliary Overvoltage (Read/Write Grouped Setting) (2 modules)
7FA0
Auxiliary Overvoltage 1 Function
7FA1
Auxiliary Overvoltage 1 Signal Source
7FA2
Auxiliary Overvoltage 1 Pickup
7FA3
Auxiliary Overvoltage 1 Pickup Delay
7FA4
Auxiliary Overvoltage 1 Reset Delay
7FA5
Auxiliary Overvoltage 1 Block
7FA7
Auxiliary Overvoltage 1 Target
7FA8
Auxiliary Overvoltage 1 Events
7FA9
Reserved (8 items)
7FB1
...Repeated for Auxiliary Overvoltage 2
Frequency (Read Only)
8000
Tracking Frequency
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 3
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 65535
2 to 90
G30 Generator Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F116
0 (Definite Time)
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
0 (Definite Time)
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
DEFAULT
B
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
700
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0
B-45

Advertisement

Table of Contents
loading