Neutral Current - GE G30 Instruction Manual

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

5 SETTINGS
The phase directional element responds to the forward load current. In the case of a following reverse fault, the ele-
ment needs some time – in the order of 8 ms – to establish a blocking signal. Some protection elements such as
NOTE
instantaneous overcurrent may respond to reverse faults before the blocking signal is established. Therefore, a
coordination time of at least 10 ms must be added to all the instantaneous protection elements under the supervi-
sion of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms –
may be needed.
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
 NEUTRAL CURRENT
MESSAGE
MESSAGE
MESSAGE
GE Multilin
Figure 5–62: PHASE DIRECTIONAL SCHEME LOGIC

SETTING GROUP 1(6)
 NEUTRAL TOC1
 NEUTRAL IOC1
 NEUTRAL
 DIRECTIONAL OC1
 NEUTRAL
 DIRECTIONAL OC2
G30 Generator Protection System
5.6 GROUPED ELEMENTS

5.6.5 NEUTRAL CURRENT

NEUTRAL CURRENT
See page 5–168.
See page 5–169.
See page 5–170.
See page 5–170.
5
5-167

Advertisement

Table of Contents
loading

Table of Contents