GE G30 Instruction Manual page 532

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 64)
ADDR
REGISTER NAME
Source Current THD and Harmonics (Read Only) (4 modules)
2800
Ia THD for Source 1
2801
Ia Harmonics for Source 1 - 2nd to 25th (24 items)
2821
Ib THD for Source 1
2822
Ib Harmonics for Source 1 - 2nd to 25th (24 items)
B
283A
Reserved (8 items)
2842
Ic THD for Source 1
2843
Ic Harmonics for Source 1 - 2nd to 25th (24 items)
285B
Reserved (8 items)
2863
...Repeated for Source 2
28C6
...Repeated for Source 3
2929
...Repeated for Source 4
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
Expanded Contact Input/Output States (Read Only)
2D00
Contact Input States, one per register (96 items)
2D80
Contact Output States, one per register (64 items)
2E00
Virtual Output States, one per register (96 items)
Expanded Remote Input/Output Status (Read Only)
2F00
Remote Device States, one per register (32 items)
2F80
Remote Input States, one per register (64 items)
Oscillography Values (Read Only)
3000
Oscillography Number of Triggers
3001
Oscillography Available Records
3002
Oscillography Last Cleared Date
3004
Oscillography Number Of Cycles Per Record
Oscillography Commands (Read/Write Command)
3005
Oscillography Force Trigger
3011
Oscillography Clear Data
Oscillography Analog Values (Read Only)
3012
Oscillography Number of Triggers
User-Programmable Fault Report Commands (Read/Write Command)
3060
User Fault Report Clear
User-Programmable Fault Report Actual Values (Read Only)
3070
Newest Record Number
3071
Cleared Date
3073
Report Date (10 items)
User-Programmable Fault Report (Read/Write Setting) (2 modules)
3090
Fault Report 1 Fault Trigger
3092
Fault Report 1 Function
3093
Fault Report 1 Prefault Trigger
3095
Fault Report Analog Channel 1 (32 items)
30B5
Fault Report 1 Reserved (5 items)
30BA
...Repeated for Fault Report 2
Modbus File Transfer (Read/Write)
3100
Name of file to read
Modbus File Transfer Values (Read Only)
3200
Character position of current block within file
3202
Size of currently-available data block
3203
Block of data from requested file (122 items)
Security (Read/Write Setting)
3280
Administrator Alphanumeric Password Setting
Security (Read Only)
328A
Administrator Alphanumeric Password Status
B-20
RANGE
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 0.1
0 to 99.9
0 to 99.9
0 to 0.1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 400000000
0 to 65535
0 to 1
0 to 1
0 to 32767
0 to 1
0 to 65535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 4294967295
0 to 65536
---
---
0 to 4294967295
0 to 65535
0 to 65535
---
0 to 1
G30 Generator Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
1
F108
---
1
F108
---
1
F108
---
1
F108
---
1
F155
---
1
F108
---
1
F001
---
1
F001
---
1
F050
---
1
F001
---
1
F126
---
1
F126
---
1
F001
---
1
F126
---
1
F001
---
1
F050
---
1
F050
---
1
F300
---
1
F102
---
1
F300
---
1
F600
---
---
F001
---
---
F204
---
1
F003
---
1
F001
---
1
F001
---
---
F202
---
1
F102
DEFAULT
0
0
0
0
0
0
0
0
0 (Off)
0 (Off)
0 (Off)
0 (Off)
0 (Offline)
0 (Off)
0
0
0
0
0 (No)
0 (No)
0
0 (No)
0
0
0
0
0 (Disabled)
0
0
0
(none)
0
0
0
(none)
0 (Disabled)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents