5 SETTINGS
GEN UNBAL STG1 K-RESET: This setting defines the linear reset rate of the stage 1 element. It is the maximum reset
time from the threshold of tripping. This feature provides a thermal memory of previous unbalance conditions.
GEN UNBAL STG2 PICKUP: This setting defines the pickup of the stage 2 element expressed as a percentage of the
nominal current as specified by
an alarm to prompt an operator to take some corrective action. The stage 2 element would typically be set at a safe
margin below the stage 1 pickup setting.
GEN UNBAL STG2 PKP DELAY: This is the minimum operate time of the stage 2 element. This is set to prevent nui-
sance alarms during system faults.