APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 64)
ADDR
REGISTER NAME
Third Harmonic Neutral Undervoltage (Read/Write Grouped Setting)
66DA
Third Harmonic Neutral Undervoltage Function
66DB
Third Harmonic Neutral Undervoltage Pickup
66DD
Third Harmonic Neutral Undervoltage Delay
66DE
Third Harmonic Neutral Undervoltage Max Power
66E0
Third Harmonic Neutral Undervoltage Min Power
66E2
Third Harmonic Neutral Undervoltage Volt Supervision
66E3
Third Harmonic Neutral Undervoltage Block
66E5
Third Harmonic Neutral Undervoltage Target
66E6
Third Harmonic Neutral Undervoltage Events
66E7
Reserved (4 items)
Generator Unbalance (Read/Write Grouped Setting)
66F0
Generator Unbalance Function
66F1
Generator Unbalance Source
66F2
Generator Unbalance Inom
66F3
Generator Unbalance Stage 1 Pickup
66F4
Generator Unbalance Stage 1 K value
66F5
Generator Unbalance Stage 1 Tmin
66F6
Generator Unbalance Stage 1 Tmax
66F7
Generator Unbalance Stage 1 K Reset
66F8
Generator Unbalance Stage 2 Pickup
66F9
Generator Unbalance Stage 2 Pickup Delay
66FA
Generator Unbalance Block
66FC
Generator Unbalance Target
66FD
Generator Unbalance Events
66FE
Reserved (3 items)
Stator Ground Source (Read/Write Grouped Setting)
670A
Stator Ground Source
Stator Ground (Read/Write Grouped Setting
6720
Stator Ground Function
6721
Stator Ground Stage 1 Pickup
6722
Stator Ground Stage 1 Pickup Delay
6723
Stator Ground Stage 1 Supv
6724
Stator Ground Stage 2 Pickup
6725
Stator Ground Stage 2 Pickup Delay
6726
Stator Ground Stage 2 Supv
6727
Stator Ground Block
6729
Stator Ground Target
672A
Stator Ground Event
672B
Reserved (5 items)
Split Phase Protection (Read/Write Grouped Setting)
6730
Split Phase Protection Function
6731
Split Phase Protection Source
6732
Split Phase Protection Load Source
6733
Split Phase Protection Phase A Pickup
6734
Split Phase Protection Phase A Offset
6735
Split Phase Protection Phase A Slope
6736
Split Phase Protection Phase B Pickup
6737
Split Phase Protection Phase B Offset
6738
Split Phase Protection Phase B Slope
6739
Split Phase Protection Phase C Pickup
673A
Split Phase Protection Phase C Offset
673B
Split Phase Protection Phase C Slope
673C
Split Phase Protection Minimum Load
GE Multilin
RANGE
0 to 1
0 to 3
0 to 600
0 to 1.25
0 to 1.25
0 to 1.25
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 1.25
0 to 100
0 to 100
0 to 50
0 to 1000
0 to 1000
0 to 100
0 to 1000
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 5
0 to 1
0 to 0.9
0 to 600
0.001 to 0.1
0 to 0.9
0 to 600
0.001 to 0.1
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 5
0.02 to 1.500
0 to 1
0 to 100
0.02 to 1.5
0 to 1
0 to 100
0.02 to 1.5
0 to 1
0 to 100
0 to 1
G30 Generator Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
pu
0.0001
F003
s
0.01
F001
pu
0.001
F003
pu
0.001
F003
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
%
0.01
F001
---
0.01
F001
s
0.001
F001
s
0.1
F001
s
0.1
F001
%
0.01
F001
s
0.1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F167
---
1
F102
pu
0.001
F001
s
0.01
F001
pu
0.0001
F001
pu
0.001
F001
s
0.01
F001
pu
0.0001
F001
---
---
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F167
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.01
F001
DEFAULT
0 (Disabled)
3000
0
200
B
200
500
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
800
800
100
250
6000
2400
300
50
0
0 (Self-reset)
0 (Disabled)
0
0 (SRC 1)
0 (Disabled)
150
100
57
150
0
45
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC1)
0 (SRC1)
200
0
0
200
0
0
200
0
0
0
B-41