GE G30 Instruction Manual page 172

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
UR relays implement only the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy
(HSR) protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 ver-
sion. The revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0.
The UR relays support only PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Port 2 and 3 of the CPU module. Use the previous sec-
tion (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Port 2 and 3) operate in redundant
mode. In this mode, Port 3 uses the Mac, IP address, and mask of Port 2.
g) ROUTING
PATH: SETTINGS
PRODUCT SETUP
 IPV4 ROUTING
 TABLE
5
A default route and a maximum number of six static routes can be configured.
The default route is used as the last choice when no other route towards a given destination is found.
 IPV4 DEFAULT ROUTE
 IPV4 STATIC
 NETWORK ROUTE 1
Configure the network IP and subnet settings before configuring the routing settings.
ADDING AND DELETING STATIC ROUTES
Host routes are not supported at present.
The routing table configuration is available on the serial port and front panel. This is a deliberate decision, to avoid loss of
connectivity when remotely configuring the UR.
By default the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This is equivalent to saying that the
static routes are not configured. When the destination address is 127.0.0.1, the mask and gateway must be also kept on
default values.
By default, the value of the route gateway address is 127.0.0.1. This means the default route is not configured.
To add a route:
5-32

COMMUNICATIONS
 IPV4 DEFAULT ROUTE
 IPV4 STATIC
MESSAGE
 NETWORK ROUTE 1
 IPV4 STATIC
MESSAGE
 NETWORK ROUTE 6
GATEWAY ADDRESS
127.0.0.1
RT1 DESTINATION:
127.0.0.1
RT1 NET MASK:
MESSAGE
255.0.0.0
RT1 GATEWAY:
MESSAGE
127.0.0.1
G30 Generator Protection System

ROUTING 1(6)
Range: Standard IPV4 unicast address format
Range: Standard IPV4 address format
Range: Standard IPV4 subnet mask format
Range: Standard IPV4 unicast address format
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents