B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 40 of 64)
ADDR
REGISTER NAME
FlexElement (Read/Write Setting) (16 modules)
9000
FlexElement 1 Function
9001
FlexElement 1 Name
9004
FlexElement 1 InputP
9005
FlexElement 1 InputM
B
9006
FlexElement 1 Compare
9007
FlexElement 1 Input
9008
FlexElement 1 Direction
9009
FlexElement 1 Hysteresis
900A
FlexElement 1 Pickup
900C
FlexElement 1 DeltaT Units
900D
FlexElement 1 DeltaT
900F
FlexElement 1 Pickup Delay
9010
FlexElement 1 Reset Delay
9011
FlexElement 1 Block
9013
FlexElement 1 Target
9014
FlexElement 1 Events
9015
...Repeated for FlexElement 2
902A
...Repeated for FlexElement 3
903F
...Repeated for FlexElement 4
9054
...Repeated for FlexElement 5
9069
...Repeated for FlexElement 6
907E
...Repeated for FlexElement 7
9093
...Repeated for FlexElement 8
90A8
...Repeated for FlexElement 9
90BD
...Repeated for FlexElement 10
90D2
...Repeated for FlexElement 11
90E7
...Repeated for FlexElement 12
90FC
...Repeated for FlexElement 13
9111
...Repeated for FlexElement 14
9126
...Repeated for FlexElement 15
913B
...Repeated for FlexElement 16
DCmA Outputs (Read/Write Setting) (24 modules)
9360
DCmA Output 1 Source
9361
DCmA Output 1 Range
9362
DCmA Output 1 Minimum
9364
DCmA Output 1 Maximum
9366
...Repeated for DCmA Output 2
936C
...Repeated for DCmA Output 3
9372
...Repeated for DCmA Output 4
9378
...Repeated for DCmA Output 5
937E
...Repeated for DCmA Output 6
9384
...Repeated for DCmA Output 7
938A
...Repeated for DCmA Output 8
9390
...Repeated for DCmA Output 9
9396
...Repeated for DCmA Output 10
939C
...Repeated for DCmA Output 11
93A2
...Repeated for DCmA Output 12
93A8
...Repeated for DCmA Output 13
93AE
...Repeated for DCmA Output 14
93B4
...Repeated for DCmA Output 15
93BA
...Repeated for DCmA Output 16
93C0
...Repeated for DCmA Output 17
93C6
...Repeated for DCmA Output 18
B-48
RANGE
0 to 1
---
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
0.1 to 50
-90 to 90
0 to 2
20 to 86400
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 2
–90 to 90
–90 to 90
G30 Generator Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
---
F206
---
1
F600
---
1
F600
---
1
F516
---
1
F515
---
1
F517
%
0.1
F001
pu
0.001
F004
---
1
F518
0 (Milliseconds)
---
1
F003
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F600
---
1
F522
0 (–1 to 1 mA)
pu
0.001
F004
pu
0.001
F004
DEFAULT
0 (Disabled)
"FxE 1"
0
0
0 (LEVEL)
0 (SIGNED)
0 (OVER)
30
1000
20
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
1000
GE Multilin