5.6 GROUPED ELEMENTS
5
Figure 5–78: SPLIT PHASE PROTECTION OPERATING CHARACTERISTICS
SPLIT PHASE FUNCTION: This setting enables and disables the function.
SPLIT PHASE SOURCE: This setting specifies a signal source used to provide current from the split phase CT to the
split phase protection.
SPLIT PHASE LOAD SOURCE: This setting specifies a signal source used to provide current from the load CT to the
split phase protection.
SPLIT PHASE A(C) PICKUP: This setting specifies a pickup level for each phase. This should be set less than the
minimum expected unbalance (split phase) current due to an inter-turn fault.