GE G30 Instruction Manual page 305

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

5 SETTINGS
e) PHASE DIRECTIONAL OVERCURRENT (ANSI 67P, IEC PDOC/PTOC)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 DIRECTIONAL 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The TARGET setting is not user-selectable and forced to "Disabled". If Targets are required from directional
elements, it can be achieved by assigning directional element output to a digital element, where targets
selection can be used as required.
NOTE
The phase directional elements (one for each of phases A, B, and C) determine the phase current flow direction for steady
state and fault conditions and can be used to control the operation of the phase overcurrent elements via the
of these elements.
Phasors for Phase A Polarization:
VPol = VBC
IA = operating current
ECA = Element Characteristic Angle at 30°
GE Multilin
SETTING GROUP 1(6)
PHASE DIR 1
FUNCTION: Disabled
PHASE DIR 1 SIGNAL
SOURCE: SRC 1
PHASE DIR 1 BLOCK:
Off
PHASE DIR 1
ECA: 30
PHASE DIR
POL V1
THRESHOLD: 0.700 pu
PHASE DIR 1 BLOCK
WHEN V MEM EXP: No
PHASE DIR 1
TARGET: Self-reset
PHASE DIR 1
EVENTS: Disabled
VAG (Unfaulted)
VAG(Faulted)
VBC
VCG
×
(1/_ECA) = polarizing voltage
Figure 5–61: PHASE A DIRECTIONAL POLARIZATION
G30 Generator Protection System
5.6 GROUPED ELEMENTS
PHASE CURRENT
PHASE DIRECTIONAL 1
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic operand
Range: 0 to 359° in steps of 1
Range: 0.000 to 3.000 pu in steps of 0.001
Range: No, Yes
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
–90°
Fault angle
set at 60° Lag
VPol
IA
ECA
set at 30°
VBC
VBG
+90°
827800A2.CDR
5
inputs
BLOCK
5-165