These modules are then freely assignable to ports E, F, N, or P of the device, see
the selected port in the (_:10621:104) Port. This parameter is automatically managed by DIGSI and
cannot be changed.
[sccommod-140213-01.tif, 1, en_US]
Figure 10-10
NOTE
i
i
Port M of the CB202 plug-in module assembly is used to accommodate measuring-transducer modules and
cannot be used for the installation of communication modules.
Addressing
You must configure the respective Ethernet address (IP address, subnet mask, etc.) for each communication
module in DIGSI. This is done in the DIGSI General settings properties dialog of the communication module in
item Ethernet addresses and so forms the IP address for the respective PMU.
[scethern-210415, 1, en_US]
Figure 10-11
In the DIGSI properties dialog for channel 1, select the synchrophasor protocol, see the following figure.
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Placement of Communication Modules
Ethernet Address Configuration
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)
Figure
10-10. You can view
1333