Supply Of Temper Coolant; Cooling Circuit; Table 9: Supply Of Temper Coolant - KEB COMBIVERT F5 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

ANNex - cOOLING SySTeM
c.1.7 Supply of temper coolant
This is possible by using heatings in the cooling circuit for the control of the coolant tem-
perature. The following dew point table is available for this:
Coolant inlet temperature [°C] is depending on ambient temperature [°C] and air humid-
ity [%]:
Air humidity [%]
Surrounding
temperature [°c]
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
Table 9:

Supply of temper coolant

c.1.8 cooling circuit
The cooling circuit must be completely empty if a unit shall be switched off for a longer
period. The cooling circuit must be blown out additionally with compressed air at tem-
peratures below 0 °C.
74
10
20
30
40
-45
-40
-36
-34
-42
-36
-32
-29
-37
-31
-27
-24
-34
-26
-22
-19
-29
-22
-18
-15
-26
-19
-14
-11
-23
-15
-11
-7
-19
-11
-7
-3
-18
-7
-3
1
-12
-4
1
5
-8
0
5
10
-6
3
10
14
-2
8
14
18
1
11
18
22
4
15
22
27
8
19
28
32
Coolant inlet temperature [°C]
50
60
70
80
-32
-30
-29
-27
-27
-25
-24
-22
-22
-20
-18
-16
-17
-15
-13
-11
-13
-11
-8
-7
-8
-6
-4
-3
-5
-2
0
2
0
1
4
6
4
7
9
11
9
12
14
16
13
16
19
21
18
21
24
26
22
25
28
31
27
31
33
36
32
36
38
41
36
40
43
45
90
100
-26
-25
-21
-20
-15
-15
-11
-10
-6
-5
-2
0
3
5
8
9
13
15
18
20
23
25
28
30
33
35
38
40
43
45
48
50

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combivert f6

Table of Contents