Messages On Display - ATTACK PELLET 30 AUTOMATIC Plus Instructions For Use Manual

Biomass boiler
Hide thumbs Also See for PELLET 30 AUTOMATIC Plus:
Table of Contents

Advertisement

Messages on display

Stand-by mode
PAUSE
OFF
FC: 0 %
Step 1 Test blowing
TEST-BLOWING
ON
FC: ? %
Step 2 Heat-up fuel feed
IGNITION 1
ON
FC: ? %
Step 3 Transition phase
TRANS.PHASE
ON
Step 4 Combustion
COMBUST
ON
Step 5 Burn-down
FINAL-COMBUST
OFF
FC: ? %
Step 6 Cleaning
SCRAPING
OFF
FC: 0 %
Step 7 Ash removing
STOKERTIME
OFF
FC: 0 %
Step 8: Return into standby mode.
Nothing operates in the burner, burner awaits start signal from
thermostat.
Thermostat turns on.
Ventilator starts to work, and when photocell measures value lower
than 5%, program continues.
Heat-up fuel feed is supplied into burner and program awaits
„flame" signal from photocell.
Transition phase begins, when photocell and control system detect
??KW
flame. Small, continually increasing amounts of pellets are feeded
into burner, unless the necessary pellet dosis is achieved.
FC: ? %
Combustion phase runs, until it is aborted by thermostat.
??KW
FC: ? %
Thermostat aborted combustion phase and burner begins the burn-
down phase.
Grate moves out. When it is completely shifted out, ventilator works
at full output, until it moves back.
Gear of ash removing is started after determined period (e.g. 6
hours) and it works within the stated time (e.g. within 3 min).