Reset Of The Regulator´s Production Settings; Exit From Service Menu; Error Messages - ATTACK DPX15 Instructions For Use Manual

Dpx wood gasifying boiler standard / profi / lambda
Hide thumbs Also See for DPX15:
Table of Contents

Advertisement

3.9 RESET OF THE REGULATOR´S PRODUCTION SETTINGS
There is a possibility to reset the production settings of the regulator by selecting the [Prod] in
the service menu and confirming by „OK" button. Then is the regulator set to the values given in
the Table 3.

3.10 EXIT FROM SERVICE MENU

Select the [End] on display and press the „OK" button to exit from service menu.

3.11 ERROR MESSAGES

The connection of all sensors of the regulator is permanently monitored. If the regulator detects
that some of the sensors is not connected, the error messages are displayed. Messages about the
boiler overheating or fuel shortage are also displayed.
Error messages displayed
[FUEL] – is displayed, when there is not enough fuel in the boiler. The sufficient amount of fuel is
c
defined by the parameter
90, where the figure 90 is related to the adjusted value 90 °C. Then, if
the flue gas temperature decreases under this adjusted value within the time Fb30 (time of
boiler stop by fuel shortage), the regulator displays the [FUEL] message. To start the boiler again,
it is necessary to remove the message by the STOP button and then to press the START.
[HOT] – is displayed, when the flue gas temperature exceeds the maximum permitted value set
by the parameter c300 (means 300 °C). The ventilator is stopped in this case. After the
temperature decreases under the adjusted flue gas temperature, the ventilator is started again.
[E 1] – is displayed, when the boiler temperature sensor fails or when it is not connected. In such
case is the regulator taking actions to ensure the safety of the boiler – the fan is stopped (if it is
currently in operation) and the circuit pump is started for eventual safe boiler cooling. After the
cause of error is removed, the error message can be erased by the STOP button.
[E 2] – is displayed, when the boiler temperature exceeds the boiler overheating temperature
A99. The regulator stops the flue gas fan and starts the circuit pump. The error message can be
removed by the STOP button after the boiler temperature decreases to the safe value.
[E 8] – is displayed, when the additional sensor fails (in the D.H.W. tank or accumulation tank). If
this sensor works for the D.H.W. tank, the warming is blocked. If the sensor works for the
accumulation tank, the pump will be permanently working. This error message cannot be
removed by the STOP button. It is automatically erased after the sensor failure is repaired.
[E128] – is displayed, when the flue gas temperature sensor fails. In this case is the boiler control
switched to regulate according to the boiler temperature. The error message is erased
automatically after the fault of the flue gas temperature sensor is solved.
[E 3] If several failures occur in one moment, their total is displayed. In such case it is necessary to
check the functionality of all sensors.