Advanced menu
Following data/parameters are adjustable by qualified person only.
All aspects of the advanced menu are available by pressing the „S" button. Actual setting is
permanently indicated in the left bottom corner by „O:" (time/value), while new value is given in
the right buttom corner by „N:" (time/value).
To increase and decrease time or values, press buttons „+" and „–". To confirm and save new
values, press „S". To exit without saving, press „ESC".
To enter into advanced menu, add 5 to the displayed random number. Example: there can be „18"
by both – „O:" and „N:". Now, press „+", unless „N:18" changes to „N:23" and press „S". Thereby
it is enabled to enter into the advanced menu.
Example:
MENU/ADVANCED
O: 18
Old
New
Output setting:
EFFECT ADJ.
ENTER
>
corner appears „OUTPUT 1 (kW)" and in the left bottom corner appears „O:14" (i.e. actual value of
the final output in kW). Then, the second output level is displayed („OUTPUT 2") to be set to the
required value. If you do not with to change it, press „S" to save the displayed value (e.g. „N:22" –
OUTPUT 2 – thereby, the second output level will be 22 kW).
To let display without saving changes, press „ESC".
Ignition setting:
IGNITION
ENTER
<
>
After pressing „S", the „Ignition dosis 1" is displayed in the left upper corner . Changes are made in
%, first dosis had been pre-set to 170 g. If you increase this amount to 110 %, the first dosis will be
changed to 187 g.
If the first trial of burner ignition fails, the „Ignition dosis 2" is activated. It is set by production to
45% from 170 g, i.e. 76,5 g.
32
Code
PEL9700
PED150A
PED250
N: 23
Here you can select three outputs as FINAL OUTPUTS in
generally accessible menu (8–30 kW).
EXIT
When you press „S" by „EFFECT ADJ." message, in the left upper
Here you can adjust ignition fuel feed in %. This value had been
automatically calculated adequately to the weight entered by the
EXIT
feeder setting – amount.