Group E0: Input Terminal Parameters

E0.00
2-wire / 3-wire running control
Setting range
0 ~ 2
Minimum unit
1
Factory default
0
In order to run the frequency converter with "2-wire / 3-wire running control", [b1.02] /
[b1.17] needs to be set as 1.
For example: one terminal is assigned as FWD ( [E0.01]=23) and connected to K1; an‐
other terminal is assigned as REV ( [E0.02]=24) and connected to K2.
● [E0.00]=0: Forward / Stop, Reverse / Stop
Fig.8-27: 2-wire control_1
K1
Inactive
Inactive
Active
Active
If both terminals are active at the same time, the frequency converter
stops according to the stopping mode configured [b1.40] and both direc‐
tions LEDs (FWD and REV) are switched on.
K2
Inactive
Active
Inactive
Active
Bosch Rexroth AG
Parameter Settings
Running status
Stop
Reverse
Forward
Stop